Vibe 19 open fdd vibe coder rule to plot catalog with haystack tags

Rule plot catalog (all 50)

Audience: agents / engineers reviewing Plots validation cards and FDD DOCX.

One section per cookbook rule, grouped by mechanical family (same order as sidebar / Results). Each chart plots required (+ optional) roles present on the mapped frame, plus a confirmed-fault swim lane.

Source Path
Catalog app/rules/cookbook_catalog.py
Haystack export map app/column_map_json.py → COOKBOOK_TO_HAYSTACK_POINT
Gates app/rules/operational_gate.py → RULE_GATES
Chart API app/charts.py → rule_result_chart
UX contract PLOTS_DOCX_VALIDATION.md
Machine inventory configs/rule_inventory.yaml (regenerate: scripts/generate_rule_configs.py)

Haystack note: Preferred tags come from COOKBOOK_TO_HAYSTACK_POINT. Roles not in that dict use the extended names in Appendix B (hyphenated Project Haystack–style).

Sliders: sidebar Rule tuning by category; values live in session_state.params[rule_id]. Confirm delay is usually confirm_min (minutes) even when catalog confirm_seconds differs.


Index by family

Family Count Rule ids
1 · Sensor validation 4 SV-RANGE, SV-FLATLINE, SV-SPIKE, SV-STALE
2 · Control loops 1 PID-HUNT-1
3 · AHU / air handling 29 FC1, FC2, FC3, FC4, FC5, FC6, FC7, FC8, FC9, FC10, FC11, FC12, FC13, FC14, FC15, AHU-SATDEV, AHU-DUCTHI, AHU-SIMUL, OAT-METEO, ECON-1, ECON-2, ECON-3, ECON-4, ECON-5, SCHED-1, CMD-1, OA-1, DMP-1, VLV-1
4 · VAV / terminal 6 VAV-1, VAV-3, VAV-4, VAV-5, VAV-REHEAT, VAV-7
5 · Central plant 5 CHW-1, CHW-2, CHW-3, CHW-4, CW-OPT-1
6 · Heat pump 1 HP-1
7 · Weather / OAT 1 WX-1
8 · Trim & respond 3 TRIM-1, TRIM-3, TRIM-4

1 · Sensor validation

SV-RANGE — Sensor out of hard range

Equation: Any modeled sensor reads outside its physical hard range (e.g. OAT −60–130°F, SAT 30–150°F, CHWS 30–80°F).

Field Value
Family sensor
Equipment kinds ahu, vav, chiller, boiler, weather, zone, heatpump
Operational gate always
Default confirm 300s
Sweep sensor_sweep

Points → Haystack tags (this chart)

Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.

Plot series

  • Present sweep sensors (temps / statuses on mapped frame)
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Plots sensor-fault summary stats when FAULT; Export sensor fault CSV.

SV-FLATLINE — Sensor flatline (stuck)

Equation: Sensor value unchanged (Δ ≤ tolerance) across the flatline window — stuck / frozen sensor.

Field Value
Family sensor
Equipment kinds ahu, vav, chiller, boiler, weather, zone, heatpump
Operational gate conditional
Default confirm 300s
Sweep sensor_sweep

Points → Haystack tags (this chart)

Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.

Plot series

  • Present sweep sensors (temps / statuses on mapped frame)
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
flatline_tol Flatline tolerance °F 0.1 0.02 1 0.02
flatline_hours Flatline window h 1 0.5 8 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Plots sensor-fault summary stats when FAULT.

SV-SPIKE — Sensor rate-of-change spike

Equation: Sample-to-sample jump exceeds the physical spike limit for the sensor type.

Field Value
Family sensor
Equipment kinds ahu, vav, chiller, boiler, weather, zone, heatpump
Operational gate always
Default confirm 300s
Sweep sensor_sweep

Points → Haystack tags (this chart)

Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.

Plot series

  • Present sweep sensors (temps / statuses on mapped frame)
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
spike_scale Spike limit scale × 1 0.25 3 0.25
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Plots sensor-fault summary stats when FAULT.

SV-STALE — Stale data (no fresh samples)

Equation: All modeled sensors unchanged over the stale window — data feed likely dropped.

Field Value
Family sensor
Equipment kinds ahu, vav, chiller, boiler, weather, zone, heatpump
Operational gate always
Default confirm 300s
Sweep sensor_sweep

Points → Haystack tags (this chart)

Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.

Plot series

  • Present sweep sensors (temps / statuses on mapped frame)
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
stale_hours Stale window h 2 0.5 12 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Plots sensor-fault summary stats when FAULT.


2 · Control loops

PID-HUNT-1 — Suspected control-output hunting

Equation: Rolling 1h total variation of any 0–100% control output (dampers, valves, fan speeds, heat/cool cmds) with span ≥20%, TV ≥500 %·pts, ≥2.5 equivalent cycles, ≥4 reversals — suspected loop hunting (not proof of bad PID alone).

Field Value
Family control
Equipment kinds ahu, vav, chiller, boiler, heatpump
Operational gate control_loop (startup 300s)
Default confirm 0s
Sweep control_output_sweep

Points → Haystack tags (this chart)

Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.

Cookbook role Haystack-like tag Requirement
loop_enabled loop-enabled optional

Plot series

  • Present 0–100% control outputs (dampers / valves / fan cmds)
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
change_deadband_pct Ignore changes below % out 1 0 10 0.5
minimum_span_pct Minimum observed span % out 20 5 100 5
total_variation_fault_pct Total travel threshold %/h 500 50 2000 50
minimum_equivalent_cycles Min equivalent cycles cyc/h 2.5 0.5 20 0.5
minimum_reversals Min direction reversals count 4 1 40 1
minimum_coverage_pct Minimum data coverage % 80 25 100 5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.


3 · AHU / air handling

FC1 — Duct static below SP at full fan (GL36 A)

Equation: Fan ≥ 87% AND duct static < static SP − 0.12 in.w.c.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
duct_static duct-static-pressure required
duct_static_sp duct-static-pressure-sp required
fan_cmd fan-cmd required

Plot series

  • duct_static → duct-static-pressure
  • duct_static_sp → duct-static-pressure-sp
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
duct_static_err Duct static error in. w.c. 0.12 0.02 0.5 0.01
fan_hi Fan high threshold frac 0.87 0.5 1 0.01
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC2 — MAT below OAT/RAT envelope (GL36 B)

Equation: Fan on AND MAT − 1.15°F < min(RAT, OAT) − 1.15°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
oa_t outside-air-temp required
rat return-air-temp required
fan_cmd fan-cmd required

Plot series

  • mat → mixed-air-temp
  • oa_t → outside-air-temp
  • rat → return-air-temp
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
mix_tol Mixing tolerance °F 1.15 0.25 3 0.05
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC3 — MAT above OAT/RAT envelope (GL36 C)

Equation: Fan on AND MAT − 1.15°F > max(RAT, OAT) + 1.15°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
oa_t outside-air-temp required
rat return-air-temp required
fan_cmd fan-cmd required

Plot series

  • mat → mixed-air-temp
  • oa_t → outside-air-temp
  • rat → return-air-temp
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
mix_tol Mixing tolerance °F 1.15 0.25 3 0.05
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC4 — PID hunting (operating-state oscillation)

Equation: More than 5 operating-mode entry transitions in any hour (heating/econ/mech modes).

Field Value
Family ahu
Equipment kinds ahu
Operational gate control_loop (startup 300s)
Default confirm 3600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required
fan_cmd fan-cmd required

Plot series

  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
delta_os_max Max mode changes/hr count 5 2 20 1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC5 — SAT cold when heating commanded (GL36 D)

Equation: Fan on AND heating > 1% AND SAT + 1.15°F ≤ MAT − 1.15°F + 0.55°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
mat mixed-air-temp required
fan_cmd fan-cmd required
htg_valve_pct heating-valve required

Plot series

  • sat → discharge-air-temp
  • mat → mixed-air-temp
  • fan_cmd → fan-cmd
  • htg_valve_pct → heating-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
mix_tol Mixing tolerance °F 1.15 0.25 3 0.05
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC6 — Estimated OA fraction mismatch

Equation: |RAT−OAT| ≥ 5°F AND |estimated OA% − design min OA%| > 15% in heating/mech-only modes.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
oa_t outside-air-temp required
rat return-air-temp required
vav_total_flow vav-total-airflow required

Plot series

  • mat → mixed-air-temp
  • oa_t → outside-air-temp
  • rat → return-air-temp
  • vav_total_flow → vav-total-airflow
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
airflow_err OA fraction error frac 0.15 0.05 0.5 0.01
min_cfm_design Design min OA CFM cfm 5000 500 20000 500
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs AHU vav_total_flow — empty plots often data gaps.

FC7 — SAT low with full heating (GL36 E)

Equation: Fan on AND heating > 90% AND SAT < SAT SP − 1.0°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
sat_sp discharge-air-temp-sp required
fan_cmd fan-cmd required
htg_valve_pct heating-valve required

Plot series

  • sat → discharge-air-temp
  • sat_sp → discharge-air-temp-sp
  • fan_cmd → fan-cmd
  • htg_valve_pct → heating-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
sat_err SAT error °F 1 0.25 5 0.25
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC8 — SAT/MAT mismatch in economizer (GL36 F)

Equation: Economizer open, CHW < 10%, |SAT − 0.55°F − MAT| > √(1.15²+1.15²).

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
mat mixed-air-temp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • sat → discharge-air-temp
  • mat → mixed-air-temp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC9 — OAT too warm for free cooling (GL36 G)

Equation: Economizer open, CHW < 10%, OAT − 1.15°F > SAT SP − 0.55°F + 1.15°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
sat_sp discharge-air-temp-sp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • oa_t → outside-air-temp
  • sat_sp → discharge-air-temp-sp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC10 — OAT/MAT mismatch + mech cooling (GL36 H)

Equation: CHW > 1%, economizer > 90%, |MAT − OAT| > √(1.15²+1.15²).

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
oa_t outside-air-temp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • mat → mixed-air-temp
  • oa_t → outside-air-temp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC11 — OAT/MAT mismatch economizer-only (GL36 I)

Equation: CHW > 1%, economizer > 90%, OAT + 1.15°F < SAT SP − 0.55°F − 1.15°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
sat_sp discharge-air-temp-sp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • oa_t → outside-air-temp
  • sat_sp → discharge-air-temp-sp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC12 — SAT above blend in cooling (GL36 J)

Equation: CHW > 1%, SAT − 1.15°F − 0.55°F > MAT + 1.15°F at min or full economizer.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
mat mixed-air-temp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • sat → discharge-air-temp
  • mat → mixed-air-temp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC13 — SAT above SP at full cooling (GL36 K)

Equation: CHW > 1%, SAT > SAT SP + 1.0°F at min or full economizer.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
sat_sp discharge-air-temp-sp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • sat → discharge-air-temp
  • sat_sp → discharge-air-temp-sp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
sat_err SAT error °F 1 0.25 5 0.25
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC14 — CHW coil ΔT when inactive (GL36 L)

Equation: Cooling coil ΔT ≥ √(1.15²+1.15²)+0.55°F while coil should be inactive.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
clg_coil_enter_t cooling-coil-entering-temp required
clg_coil_leave_t cooling-coil-leaving-temp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • clg_coil_enter_t → cooling-coil-entering-temp
  • clg_coil_leave_t → cooling-coil-leaving-temp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

FC15 — HW coil ΔT when inactive (GL36 M)

Equation: Heating coil ΔT ≥ √(1.15²+1.15²)+0.55°F while coil should be inactive.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
htg_coil_enter_t heating-coil-entering-temp required
htg_coil_leave_t heating-coil-leaving-temp required
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • htg_coil_enter_t → heating-coil-entering-temp
  • htg_coil_leave_t → heating-coil-leaving-temp
  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

AHU-SATDEV — SAT deviation from setpoint

Equation: |SAT − SAT SP| > 5°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
sat_sp discharge-air-temp-sp required

Plot series

  • sat → discharge-air-temp
  • sat_sp → discharge-air-temp-sp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
sat_dev_err SAT deviation °F 5 1 15 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

RCx ahu_sat_reset_scatter — SAT vs web OAT.

AHU-DUCTHI — Duct static pressure high

Equation: Duct static > static SP + 0.25 in.w.c.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
duct_static duct-static-pressure required
duct_static_sp duct-static-pressure-sp required

Plot series

  • duct_static → duct-static-pressure
  • duct_static_sp → duct-static-pressure-sp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
duct_high_margin High margin in. w.c. 0.25 0.05 1 0.05
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

RCx duct_static_box (fan-on) for static-reset opportunity.

AHU-SIMUL — Heating and cooling simultaneous

Equation: Heating valve > 10% AND cooling valve > 10% at once.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
htg_valve_pct heating-valve required
clg_valve_pct cooling-valve required

Plot series

  • htg_valve_pct → heating-valve
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
valve_open_pct Valve open threshold frac 0.1 0.05 0.5 0.01
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

OAT-METEO — BAS outdoor-air sensor vs Open-Meteo

Equation: BAS OAT sensor differs from Open-Meteo dry bulb by more than 5°F.

Field Value
Family ahu
Equipment kinds ahu
Operational gate always
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
wx_oa_t web-outside-air-temp required

Plot series

  • oa_t → outside-air-temp
  • wx_oa_t → web-outside-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
oat_err Max OAT disagreement °F 5 2 20 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs both BAS oa_t and web wx_oa_t; Prefer web OAT sidebar.

ECON-1 — Economizer stuck closed

Equation: Fan on, OA damper < 5%, OAT > 55°F (should be economizing).

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
fan_cmd fan-cmd required
oa_damper_pct outside-air-damper required
oa_t outside-air-temp required

Plot series

  • fan_cmd → fan-cmd
  • oa_damper_pct → outside-air-damper
  • oa_t → outside-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
econ1_oat_min Favorable OAT °F 55 45 70 1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs OA damper / MAT / OAT roles (oa_damper_pct e.g. mad_c).

ECON-2 — Economizing when outdoor unfavorable

Equation: OAT > 63°F AND OA damper > 42% (should be at minimum).

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
oa_damper_pct outside-air-damper required

Plot series

  • oa_t → outside-air-temp
  • oa_damper_pct → outside-air-damper
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
econ2_oat_hi OAT high cutoff °F 63 55 80 1
econ2_damper Damper open frac frac 0.42 0.2 0.9 0.02
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs OA damper / MAT / OAT roles.

ECON-3 — Mech cooling when econ available

Equation: Free cooling available when web dry-bulb is 35–72°F AND dewpoint < 60°F (RH→dewpoint if needed); fault when cooling valve open with OA damper closed. Optional SAT≈SP means free cooling is keeping up.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_damper_pct outside-air-damper required
clg_valve_pct cooling-valve required

Plot series

  • oa_damper_pct → outside-air-damper
  • clg_valve_pct → cooling-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
econ3_db_min Free-cool OA dry-bulb min °F 35 25 45 1
econ3_db_max Free-cool OA dry-bulb max °F 72 60 80 1
econ3_dp_max Free-cool OA dew point max °F 60 45 68 1
econ3_oat_fallback Fallback OAT cutoff °F 63 55 70 1
econ3_damper Damper closed frac frac 0.32 0.1 0.6 0.02
econ3_zone_band SAT≈SP band (keeping up) °F 2 0.5 6 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Free-cool uses web dry-bulb + dewpoint (RH→Magnus); related to mech-cooling OAT bins (DX/plant only).

ECON-4 — Low estimated OA fraction

Equation: Fan on, |RAT−OAT| > 2.2°F, estimated OA fraction < 21%.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
rat return-air-temp required
oa_t outside-air-temp required
fan_cmd fan-cmd required

Plot series

  • mat → mixed-air-temp
  • rat → return-air-temp
  • oa_t → outside-air-temp
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
oa_min_pct Min OA fraction % 21 5 40 1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs OA damper / MAT / OAT roles.

ECON-5 — Preheat over-conditioning

Equation: Preheat leaving air > 2.2°F above target while preheat active.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
preheat_leave_t preheat-leaving-temp required
sat_sp discharge-air-temp-sp required
oa_t outside-air-temp required
htg_valve_pct heating-valve required

Plot series

  • preheat_leave_t → preheat-leaving-temp
  • sat_sp → discharge-air-temp-sp
  • oa_t → outside-air-temp
  • htg_valve_pct → heating-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Needs heat/preheat roles.

SCHED-1 — Unoccupied runtime

Equation: Fan running while occupancy is unoccupied (Overview calendar → occ_mode). When zone_t is mapped, also require zone inside comfort_low_f…comfort_high_f (defaults 70–75°F; synced from Overview zone band).

Field Value
Family ahu
Equipment kinds ahu
Operational gate always
Default confirm 1800s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
occ_mode occupied required
fan_status fan-status required
zone_t zone-air-temp optional

Plot series

  • occ_mode → occupied
  • fan_status → fan-status
  • zone_t → zone-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
comfort_low_f Comfort low °F 70 60 78 0.5
comfort_high_f Comfort high °F 75 68 85 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Overview occupancy calendar drives occ_mode; zone comfort band sliders (°F/°C display).

CMD-1 — Fan cmd/status mismatch

Equation: Fan command and proven status disagree.

Field Value
Family ahu
Equipment kinds ahu
Operational gate always
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
fan_cmd fan-cmd required
fan_status fan-status required

Plot series

  • fan_cmd → fan-cmd
  • fan_status → fan-status
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

OA-1 — Low OA fraction

Equation: Estimated OA fraction < 15% with adequate OAT/RAT split.

Field Value
Family ahu
Equipment kinds ahu
Operational gate fan_running (startup 600s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
mat mixed-air-temp required
rat return-air-temp required
oa_t outside-air-temp required
fan_status fan-status required

Plot series

  • mat → mixed-air-temp
  • rat → return-air-temp
  • oa_t → outside-air-temp
  • fan_status → fan-status
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
min_oa_frac Min OA fraction frac 0.15 0.05 0.4 0.01
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

DMP-1 — OA damper leakage

Equation: Damper ≤ 5% but MAT tracks OAT within 2°F — leaking OA damper.

Field Value
Family ahu
Equipment kinds ahu
Operational gate conditional (startup 300s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
mat mixed-air-temp required
oa_damper_pct outside-air-damper required

Plot series

  • oa_t → outside-air-temp
  • mat → mixed-air-temp
  • oa_damper_pct → outside-air-damper
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
leak_delta Leak ΔT °F 2 0.5 6 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VLV-1 — Cooling valve leakage

Equation: Cooling valve ≤ 5% AND (SAT < sat_sp − sat_err OR SAT < MAT − mat_leak_delta). Fan proven on when fan_status/fan_cmd present (operational gate).

Field Value
Family ahu
Equipment kinds ahu
Operational gate conditional (startup 300s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
sat_sp discharge-air-temp-sp required
clg_valve_pct cooling-valve required
mat mixed-air-temp optional
fan_status fan-status optional
fan_cmd fan-cmd optional

Plot series

  • sat → discharge-air-temp
  • sat_sp → discharge-air-temp-sp
  • clg_valve_pct → cooling-valve
  • mat → mixed-air-temp
  • fan_status → fan-status
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
sat_err SAT vs SP leak ΔT °F 2 0.5 8 0.5
mat_leak_delta SAT vs MAT leak ΔT °F 2 0.5 12 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Valve closed + SAT vs SP or SAT vs MAT; fan gate when present.


4 · VAV / terminal

VAV-1 — Zone comfort band

Equation: Zone temp < 70°F or > 75°F.

Field Value
Family vav
Equipment kinds vav, zone
Operational gate conditional
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
zone_t zone-air-temp required

Plot series

  • zone_t → zone-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
zone_lo Zone low °F 70 55 72 0.5
zone_hi Zone high °F 75 72 85 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VAV-3 — Excessive reheat during warm weather

Equation: Air flowing AND OAT > 78°F AND reheat valve > 52%.

Field Value
Family vav
Equipment kinds vav
Operational gate fan_running (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required
reheat_valve_pct reheat-valve required

Plot series

  • oa_t → outside-air-temp
  • reheat_valve_pct → reheat-valve
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
reheat_oat Warm OAT °F 78 65 90 1
reheat_pct Reheat frac frac 0.52 0.1 1 0.02
flow_on_min Airflow-on min cfm 25 0 200 5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VAV-4 — Damper stuck at full open

Equation: Air flowing AND damper > 97.5% sustained across the window.

Field Value
Family vav
Equipment kinds vav
Operational gate control_loop (startup 300s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
damper_pct damper required

Plot series

  • damper_pct → damper
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
full_open_pct Full open frac frac 0.975 0.8 1 0.005
sustain_hours Sustain window h 1.5 0.5 6 0.5
flow_on_min Airflow-on min cfm 25 0 200 5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VAV-5 — Airflow sensor bias

Equation: Airflow > 50 cfm while damper < 10% (implausible flow).

Field Value
Family vav
Equipment kinds vav
Operational gate fan_running (startup 300s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
zone_flow zone-airflow required
damper_pct damper required

Plot series

  • zone_flow → zone-airflow
  • damper_pct → damper
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VAV-REHEAT — Reheat valve stuck / no temp rise

Equation: Air flowing AND reheat valve > 30% AND box discharge temp rises < 3°F above duct inlet (air from AHU) — stuck or failed reheat valve/coil.

Field Value
Family vav
Equipment kinds vav
Operational gate fan_running (startup 600s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
reheat_valve_pct reheat-valve required
vav_disch_t vav-discharge-air-temp required
vav_inlet_t vav-inlet-air-temp required

Plot series

  • reheat_valve_pct → reheat-valve
  • vav_disch_t → vav-discharge-air-temp
  • vav_inlet_t → vav-inlet-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
reheat_cmd Reheat open frac frac 0.3 0.1 1 0.05
min_rise Min temp rise °F 3 0.5 15 0.5
flow_on_min Airflow-on min cfm 25 0 200 5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

VAV-7 — Min airflow / fixed high flow

Equation: Flow below min SP (when mapped), OR airflow stays flat (low rolling std) at a high mean while air is on (mins too high / box never modulates), OR min_flow_sp itself is excessively high.

Field Value
Family vav
Equipment kinds vav
Operational gate fan_running (startup 300s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
zone_flow zone-airflow required

Plot series

  • zone_flow → zone-airflow
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
flow_on_min Airflow-on min cfm 25 0 200 5
fixed_flow_max_std Fixed-flow max std cfm 15 1 80 1
fixed_flow_min_mean Fixed-flow min mean cfm 200 50 2000 10
high_min_flow_sp High min-flow SP cfm 250 50 2000 10
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.


5 · Central plant

CHW-1 — Low chilled-water ΔT

Equation: Pump on AND (CHWR − CHWS) < 4°F.

Field Value
Family plant
Equipment kinds chiller
Operational gate hydronic_flow (startup 900s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
chw_supply_t chilled-water-supply-temp required
chw_return_t chilled-water-return-temp required

Plot series

  • chw_supply_t → chilled-water-supply-temp
  • chw_return_t → chilled-water-return-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
min_dt Min ΔT °F 4 1 12 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

RCx chw_reset_scatter — CHW leave vs web OAT; motor weekly uses pump/status not leave-temp.

CHW-2 — DP below SP at max pump speed

Equation: Pump ≥ 87% AND CHW DP < DP SP − 2.2.

Field Value
Family plant
Equipment kinds chiller
Operational gate hydronic_flow (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
chw_dp chw-diff-pressure required
chw_dp_sp chw-diff-pressure-sp required
chw_pump_cmd chw-pump-cmd required

Plot series

  • chw_dp → chw-diff-pressure
  • chw_dp_sp → chw-diff-pressure-sp
  • chw_pump_cmd → chw-pump-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
dp_margin DP margin psi 2.2 0.5 6 0.1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Plant motor weekly / chiller runtime — status/pump proof.

CHW-3 — Plant supply temp outside deadband

Equation: Pump on AND |CHWS − CHWS SP| > 2.2°F.

Field Value
Family plant
Equipment kinds chiller
Operational gate hydronic_flow (startup 600s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
chw_supply_t chilled-water-supply-temp required
chw_supply_t_sp chilled-water-supply-temp-sp required
chw_pump_cmd chw-pump-cmd required

Plot series

  • chw_supply_t → chilled-water-supply-temp
  • chw_supply_t_sp → chilled-water-supply-temp-sp
  • chw_pump_cmd → chw-pump-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
sp_band SP band °F 2.2 0.5 6 0.1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

CHW-4 — Flow high at max pump

Equation: Pump ≥ 87% AND CHW flow > 1100 gpm.

Field Value
Family plant
Equipment kinds chiller
Operational gate hydronic_flow (startup 300s)
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
chw_flow chw-flow required
chw_pump_cmd chw-pump-cmd required

Plot series

  • chw_flow → chw-flow
  • chw_pump_cmd → chw-pump-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
flow_hi Flow high gpm 1100 200 3000 50
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.

CW-OPT-1 — Condenser water not optimized vs wet-bulb

Equation: CW supply significantly colder than web wet-bulb + design approach (Stull WB) — tower over-cooling / not optimized.

Field Value
Family plant
Equipment kinds chiller
Operational gate hydronic_flow (startup 600s)
Default confirm 900s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
cw_supply_t condenser-water-supply-temp required

Plot series

  • cw_supply_t → condenser-water-supply-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
cw_approach Design approach °F 7 3 15 0.5
cw_slack Slack below target °F 2 0.5 6 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

RCx cw_reset_scatter uses cw_supply_t vs web wet-bulb.


6 · Heat pump

HP-1 — Discharge cold when heating

Equation: Fan on, zone < 69°F, discharge SAT < 85°F.

Field Value
Family heatpump
Equipment kinds heatpump
Operational gate compressor (startup 600s)
Default confirm 600s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
sat discharge-air-temp required
zone_t zone-air-temp required
fan_cmd fan-cmd required

Plot series

  • sat → discharge-air-temp
  • zone_t → zone-air-temp
  • fan_cmd → fan-cmd
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
min_sat Min heating SAT °F 85 70 110 1
zone_cold Zone cold °F 69 60 72 0.5
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Mech-cooling OAT bins can use DX/compressor roles.


7 · Weather / OAT

WX-1 — OA temperature spike

Equation: OAT sample-to-sample jump > 16°F.

Field Value
Family weather
Equipment kinds weather
Operational gate always
Default confirm 300s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
oa_t outside-air-temp required

Plot series

  • oa_t → outside-air-temp
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
spike_limit Spike limit °F 16 4 40 1
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Weather family; web OAT enrich on weather frame.


8 · Trim & respond

TRIM-1 — Duct static trim advisory

Equation: Duct static high (> 1.35 in.w.c.) while VAV pressure requests are low.

Field Value
Family trim
Equipment kinds ahu
Operational gate fan_running (startup 300s)
Default confirm 1800s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
duct_static duct-static-pressure required
vav_press_req_sum vav-pressure-request-sum required

Plot series

  • duct_static → duct-static-pressure
  • vav_press_req_sum → vav-pressure-request-sum
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

Duct static / pressure trim requests; related to duct-static box RCx.

TRIM-3 — HWST trim advisory

Equation: HW supply > 160°F while reset requests are low.

Field Value
Family trim
Equipment kinds boiler
Operational gate hydronic_flow (startup 600s)
Default confirm 1800s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
hw_supply_t hot-water-supply-temp required
hw_reset_req_sum hw-reset-request-sum required

Plot series

  • hw_supply_t → hot-water-supply-temp
  • hw_reset_req_sum → hw-reset-request-sum
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

HW reset requests; RCx hw_reset_scatter.

TRIM-4 — CHW plant reset advisory

Equation: CHW supply < 45°F while reset requests are low.

Field Value
Family trim
Equipment kinds chiller
Operational gate hydronic_flow (startup 600s)
Default confirm 1800s
Sweep —

Points → Haystack tags (this chart)

Cookbook role Haystack-like tag Requirement
chw_supply_t chilled-water-supply-temp required
chw_reset_req_sum chw-reset-request-sum required

Plot series

  • chw_supply_t → chilled-water-supply-temp
  • chw_reset_req_sum → chw-reset-request-sum
  • confirmed_fault swim lane (bool shade) when the rule was run

Sliders (tune params)

Key Label Unit Default Min Max Step
confirm_min Fault confirm delay min 5 0 60 1

Analytics / related views

CHW reset requests; RCx chw_reset_scatter.


Appendix A — COOKBOOK_TO_HAYSTACK_POINT (canonical export)

Cookbook role Haystack-like tag
chw_dp chw-diff-pressure
chw_dp_sp chw-diff-pressure-sp
chw_flow chw-flow
chw_pump_cmd chw-pump-cmd
chw_reset_req_sum chw-reset-request-sum
chw_return_t chilled-water-return-temp
chw_supply_t chilled-water-supply-temp
chw_supply_t_sp chilled-water-supply-temp-sp
clg_coil_enter_t cooling-coil-entering-temp
clg_coil_leave_t cooling-coil-leaving-temp
clg_valve_pct cooling-valve
cw_supply_t condenser-water-supply-temp
damper_pct damper
duct_static duct-static-pressure
duct_static_sp duct-static-pressure-sp
fan_cmd fan-cmd
fan_status fan-status
htg_coil_enter_t heating-coil-entering-temp
htg_coil_leave_t heating-coil-leaving-temp
htg_valve_pct heating-valve
hw_reset_req_sum hw-reset-request-sum
hw_return_t hot-water-return-temp
hw_supply_t hot-water-supply-temp
loop_enabled loop-enabled
mat mixed-air-temp
min_flow_sp min-flow-sp
oa_damper_pct outside-air-damper
oa_t outside-air-temp
occ_mode occupied
preheat_leave_t preheat-leaving-temp
rat return-air-temp
reheat_valve_pct reheat-valve
sat discharge-air-temp
sat_sp discharge-air-temp-sp
vav_disch_t vav-discharge-air-temp
vav_inlet_t vav-inlet-air-temp
vav_press_req_sum vav-pressure-request-sum
vav_total_flow vav-total-airflow
wx_oa_t web-outside-air-temp
zone_flow zone-airflow
zone_t zone-air-temp

Appendix B — Extended Haystack-style names used in this catalog

These roles appear on rules but are not yet keys in COOKBOOK_TO_HAYSTACK_POINT. Prefer adding them to the dict when you next touch mapping exports.

Cookbook role Suggested Haystack-like tag
airflow_proof airflow-proof
compressor_status compressor-status
cool_stage cool-stage
dx_cool_cmd dx-cool-cmd
dx_cooling dx-cooling
dx_stage dx-stage
fan_current fan-current
fan_power fan-power
fan_speed_feedback fan-speed-feedback
pump_status pump-status

Appendix C — Related RCx presets (not the 50)

See RCX_PLOTS.md. Reset scatters / duct-static box share roles with plant/AHU rules above.

Appendix D — Building-level analytics (not per-rule charts)

View Where Roles / inputs
Motor weekly runtime Overview / Analytics fan/pump/compressor status preferred
Mech-cooling OAT bins Overview / Analytics plant pump/status or DX compressor; web OAT; never CHW valve %
Sensor fault summary Plots (device) sensors involved in FAULT SV-*
Occupancy calendar Overview writes occ_mode for SCHED-1