One section per cookbook rule, grouped by mechanical family (same order as sidebar / Results).
Each chart plots required (+ optional) roles present on the mapped frame, plus a confirmed-fault swim lane.
Haystack note: Preferred tags come from COOKBOOK_TO_HAYSTACK_POINT. Roles not in that dict
use the extended names in Appendix B (hyphenated Project Haystack–style).
Sliders: sidebar Rule tuning by category; values live in session_state.params[rule_id].
Confirm delay is usually confirm_min (minutes) even when catalog confirm_seconds differs.
Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.
Plot series
Present sweep sensors (temps / statuses on mapped frame)
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
stale_hours
Stale window
h
2
0.5
12
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Plots sensor-fault summary stats when FAULT.
2 · Control loops
PID-HUNT-1 — Suspected control-output hunting
Equation: Rolling 1h total variation of any 0–100% control output (dampers, valves, fan speeds, heat/cool cmds) with span ≥20%, TV ≥500 %·pts, ≥2.5 equivalent cycles, ≥4 reversals — suspected loop hunting (not proof of bad PID alone).
Field
Value
Family
control
Equipment kinds
ahu, vav, chiller, boiler, heatpump
Operational gate
control_loop (startup 300s)
Default confirm
0s
Sweep
control_output_sweep
Points → Haystack tags (this chart)
Sweep rule: plots sensors / control outputs present on the equipment (see sweep role lists in cookbook_catalog.py). No fixed required-role list.
Cookbook role
Haystack-like tag
Requirement
loop_enabled
loop-enabled
optional
Plot series
Present 0–100% control outputs (dampers / valves / fan cmds)
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
change_deadband_pct
Ignore changes below
% out
1
0
10
0.5
minimum_span_pct
Minimum observed span
% out
20
5
100
5
total_variation_fault_pct
Total travel threshold
%/h
500
50
2000
50
minimum_equivalent_cycles
Min equivalent cycles
cyc/h
2.5
0.5
20
0.5
minimum_reversals
Min direction reversals
count
4
1
40
1
minimum_coverage_pct
Minimum data coverage
%
80
25
100
5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
3 · AHU / air handling
FC1 — Duct static below SP at full fan (GL36 A)
Equation: Fan ≥ 87% AND duct static < static SP − 0.12 in.w.c.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
duct_static
duct-static-pressure
required
duct_static_sp
duct-static-pressure-sp
required
fan_cmd
fan-cmd
required
Plot series
duct_static → duct-static-pressure
duct_static_sp → duct-static-pressure-sp
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
duct_static_err
Duct static error
in. w.c.
0.12
0.02
0.5
0.01
fan_hi
Fan high threshold
frac
0.87
0.5
1
0.01
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC2 — MAT below OAT/RAT envelope (GL36 B)
Equation: Fan on AND MAT − 1.15°F < min(RAT, OAT) − 1.15°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
mat
mixed-air-temp
required
oa_t
outside-air-temp
required
rat
return-air-temp
required
fan_cmd
fan-cmd
required
Plot series
mat → mixed-air-temp
oa_t → outside-air-temp
rat → return-air-temp
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
mix_tol
Mixing tolerance
°F
1.15
0.25
3
0.05
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC3 — MAT above OAT/RAT envelope (GL36 C)
Equation: Fan on AND MAT − 1.15°F > max(RAT, OAT) + 1.15°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
mat
mixed-air-temp
required
oa_t
outside-air-temp
required
rat
return-air-temp
required
fan_cmd
fan-cmd
required
Plot series
mat → mixed-air-temp
oa_t → outside-air-temp
rat → return-air-temp
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
mix_tol
Mixing tolerance
°F
1.15
0.25
3
0.05
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC4 — PID hunting (operating-state oscillation)
Equation: More than 5 operating-mode entry transitions in any hour (heating/econ/mech modes).
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
control_loop (startup 300s)
Default confirm
3600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
fan_cmd
fan-cmd
required
Plot series
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
delta_os_max
Max mode changes/hr
count
5
2
20
1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC5 — SAT cold when heating commanded (GL36 D)
Equation: Fan on AND heating > 1% AND SAT + 1.15°F ≤ MAT − 1.15°F + 0.55°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
mat
mixed-air-temp
required
fan_cmd
fan-cmd
required
htg_valve_pct
heating-valve
required
Plot series
sat → discharge-air-temp
mat → mixed-air-temp
fan_cmd → fan-cmd
htg_valve_pct → heating-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
mix_tol
Mixing tolerance
°F
1.15
0.25
3
0.05
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC6 — Estimated OA fraction mismatch
Equation: |RAT−OAT| ≥ 5°F AND |estimated OA% − design min OA%| > 15% in heating/mech-only modes.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
mat
mixed-air-temp
required
oa_t
outside-air-temp
required
rat
return-air-temp
required
vav_total_flow
vav-total-airflow
required
Plot series
mat → mixed-air-temp
oa_t → outside-air-temp
rat → return-air-temp
vav_total_flow → vav-total-airflow
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
airflow_err
OA fraction error
frac
0.15
0.05
0.5
0.01
min_cfm_design
Design min OA CFM
cfm
5000
500
20000
500
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs AHU vav_total_flow — empty plots often data gaps.
FC7 — SAT low with full heating (GL36 E)
Equation: Fan on AND heating > 90% AND SAT < SAT SP − 1.0°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
sat_sp
discharge-air-temp-sp
required
fan_cmd
fan-cmd
required
htg_valve_pct
heating-valve
required
Plot series
sat → discharge-air-temp
sat_sp → discharge-air-temp-sp
fan_cmd → fan-cmd
htg_valve_pct → heating-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
sat_err
SAT error
°F
1
0.25
5
0.25
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC12 — SAT above blend in cooling (GL36 J)
Equation: CHW > 1%, SAT − 1.15°F − 0.55°F > MAT + 1.15°F at min or full economizer.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
mat
mixed-air-temp
required
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
Plot series
sat → discharge-air-temp
mat → mixed-air-temp
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC13 — SAT above SP at full cooling (GL36 K)
Equation: CHW > 1%, SAT > SAT SP + 1.0°F at min or full economizer.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
sat_sp
discharge-air-temp-sp
required
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
Plot series
sat → discharge-air-temp
sat_sp → discharge-air-temp-sp
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
sat_err
SAT error
°F
1
0.25
5
0.25
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC14 — CHW coil ΔT when inactive (GL36 L)
Equation: Cooling coil ΔT ≥ √(1.15²+1.15²)+0.55°F while coil should be inactive.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
clg_coil_enter_t
cooling-coil-entering-temp
required
clg_coil_leave_t
cooling-coil-leaving-temp
required
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
Plot series
clg_coil_enter_t → cooling-coil-entering-temp
clg_coil_leave_t → cooling-coil-leaving-temp
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
FC15 — HW coil ΔT when inactive (GL36 M)
Equation: Heating coil ΔT ≥ √(1.15²+1.15²)+0.55°F while coil should be inactive.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
htg_coil_enter_t
heating-coil-entering-temp
required
htg_coil_leave_t
heating-coil-leaving-temp
required
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
Plot series
htg_coil_enter_t → heating-coil-entering-temp
htg_coil_leave_t → heating-coil-leaving-temp
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
AHU-SATDEV — SAT deviation from setpoint
Equation: |SAT − SAT SP| > 5°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
sat_sp
discharge-air-temp-sp
required
Plot series
sat → discharge-air-temp
sat_sp → discharge-air-temp-sp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
sat_dev_err
SAT deviation
°F
5
1
15
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
RCx ahu_sat_reset_scatter — SAT vs web OAT.
AHU-DUCTHI — Duct static pressure high
Equation: Duct static > static SP + 0.25 in.w.c.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
duct_static
duct-static-pressure
required
duct_static_sp
duct-static-pressure-sp
required
Plot series
duct_static → duct-static-pressure
duct_static_sp → duct-static-pressure-sp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
duct_high_margin
High margin
in. w.c.
0.25
0.05
1
0.05
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
RCx duct_static_box (fan-on) for static-reset opportunity.
AHU-SIMUL — Heating and cooling simultaneous
Equation: Heating valve > 10% AND cooling valve > 10% at once.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
htg_valve_pct
heating-valve
required
clg_valve_pct
cooling-valve
required
Plot series
htg_valve_pct → heating-valve
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
valve_open_pct
Valve open threshold
frac
0.1
0.05
0.5
0.01
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
OAT-METEO — BAS outdoor-air sensor vs Open-Meteo
Equation: BAS OAT sensor differs from Open-Meteo dry bulb by more than 5°F.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
always
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_t
outside-air-temp
required
wx_oa_t
web-outside-air-temp
required
Plot series
oa_t → outside-air-temp
wx_oa_t → web-outside-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
oat_err
Max OAT disagreement
°F
5
2
20
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs both BAS oa_t and web wx_oa_t; Prefer web OAT sidebar.
ECON-1 — Economizer stuck closed
Equation: Fan on, OA damper < 5%, OAT > 55°F (should be economizing).
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
fan_cmd
fan-cmd
required
oa_damper_pct
outside-air-damper
required
oa_t
outside-air-temp
required
Plot series
fan_cmd → fan-cmd
oa_damper_pct → outside-air-damper
oa_t → outside-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
econ1_oat_min
Favorable OAT
°F
55
45
70
1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs OA damper / MAT / OAT roles (oa_damper_pct e.g. mad_c).
ECON-2 — Economizing when outdoor unfavorable
Equation: OAT > 63°F AND OA damper > 42% (should be at minimum).
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_t
outside-air-temp
required
oa_damper_pct
outside-air-damper
required
Plot series
oa_t → outside-air-temp
oa_damper_pct → outside-air-damper
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
econ2_oat_hi
OAT high cutoff
°F
63
55
80
1
econ2_damper
Damper open frac
frac
0.42
0.2
0.9
0.02
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs OA damper / MAT / OAT roles.
ECON-3 — Mech cooling when econ available
Equation: Free cooling available when web dry-bulb is 35–72°F AND dewpoint < 60°F (RH→dewpoint if needed); fault when cooling valve open with OA damper closed. Optional SAT≈SP means free cooling is keeping up.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_damper_pct
outside-air-damper
required
clg_valve_pct
cooling-valve
required
Plot series
oa_damper_pct → outside-air-damper
clg_valve_pct → cooling-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
econ3_db_min
Free-cool OA dry-bulb min
°F
35
25
45
1
econ3_db_max
Free-cool OA dry-bulb max
°F
72
60
80
1
econ3_dp_max
Free-cool OA dew point max
°F
60
45
68
1
econ3_oat_fallback
Fallback OAT cutoff
°F
63
55
70
1
econ3_damper
Damper closed frac
frac
0.32
0.1
0.6
0.02
econ3_zone_band
SAT≈SP band (keeping up)
°F
2
0.5
6
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Free-cool uses web dry-bulb + dewpoint (RH→Magnus); related to mech-cooling OAT bins (DX/plant only).
ECON-4 — Low estimated OA fraction
Equation: Fan on, |RAT−OAT| > 2.2°F, estimated OA fraction < 21%.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
mat
mixed-air-temp
required
rat
return-air-temp
required
oa_t
outside-air-temp
required
fan_cmd
fan-cmd
required
Plot series
mat → mixed-air-temp
rat → return-air-temp
oa_t → outside-air-temp
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
oa_min_pct
Min OA fraction
%
21
5
40
1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs OA damper / MAT / OAT roles.
ECON-5 — Preheat over-conditioning
Equation: Preheat leaving air > 2.2°F above target while preheat active.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
preheat_leave_t
preheat-leaving-temp
required
sat_sp
discharge-air-temp-sp
required
oa_t
outside-air-temp
required
htg_valve_pct
heating-valve
required
Plot series
preheat_leave_t → preheat-leaving-temp
sat_sp → discharge-air-temp-sp
oa_t → outside-air-temp
htg_valve_pct → heating-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Needs heat/preheat roles.
SCHED-1 — Unoccupied runtime
Equation: Fan running while occupancy is unoccupied (Overview calendar → occ_mode). When zone_t is mapped, also require zone inside comfort_low_f…comfort_high_f (defaults 70–75°F; synced from Overview zone band).
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
always
Default confirm
1800s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
occ_mode
occupied
required
fan_status
fan-status
required
zone_t
zone-air-temp
optional
Plot series
occ_mode → occupied
fan_status → fan-status
zone_t → zone-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
comfort_low_f
Comfort low
°F
70
60
78
0.5
comfort_high_f
Comfort high
°F
75
68
85
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Overview occupancy calendar drives occ_mode; zone comfort band sliders (°F/°C display).
CMD-1 — Fan cmd/status mismatch
Equation: Fan command and proven status disagree.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
always
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
fan_cmd
fan-cmd
required
fan_status
fan-status
required
Plot series
fan_cmd → fan-cmd
fan_status → fan-status
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
OA-1 — Low OA fraction
Equation: Estimated OA fraction < 15% with adequate OAT/RAT split.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
fan_running (startup 600s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
mat
mixed-air-temp
required
rat
return-air-temp
required
oa_t
outside-air-temp
required
fan_status
fan-status
required
Plot series
mat → mixed-air-temp
rat → return-air-temp
oa_t → outside-air-temp
fan_status → fan-status
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
min_oa_frac
Min OA fraction
frac
0.15
0.05
0.4
0.01
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
DMP-1 — OA damper leakage
Equation: Damper ≤ 5% but MAT tracks OAT within 2°F — leaking OA damper.
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
conditional (startup 300s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_t
outside-air-temp
required
mat
mixed-air-temp
required
oa_damper_pct
outside-air-damper
required
Plot series
oa_t → outside-air-temp
mat → mixed-air-temp
oa_damper_pct → outside-air-damper
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
leak_delta
Leak ΔT
°F
2
0.5
6
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
VLV-1 — Cooling valve leakage
Equation: Cooling valve ≤ 5% AND (SAT < sat_sp − sat_err OR SAT < MAT − mat_leak_delta). Fan proven on when fan_status/fan_cmd present (operational gate).
Field
Value
Family
ahu
Equipment kinds
ahu
Operational gate
conditional (startup 300s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
sat_sp
discharge-air-temp-sp
required
clg_valve_pct
cooling-valve
required
mat
mixed-air-temp
optional
fan_status
fan-status
optional
fan_cmd
fan-cmd
optional
Plot series
sat → discharge-air-temp
sat_sp → discharge-air-temp-sp
clg_valve_pct → cooling-valve
mat → mixed-air-temp
fan_status → fan-status
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
sat_err
SAT vs SP leak ΔT
°F
2
0.5
8
0.5
mat_leak_delta
SAT vs MAT leak ΔT
°F
2
0.5
12
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Valve closed + SAT vs SP or SAT vs MAT; fan gate when present.
4 · VAV / terminal
VAV-1 — Zone comfort band
Equation: Zone temp < 70°F or > 75°F.
Field
Value
Family
vav
Equipment kinds
vav, zone
Operational gate
conditional
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
zone_t
zone-air-temp
required
Plot series
zone_t → zone-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
zone_lo
Zone low
°F
70
55
72
0.5
zone_hi
Zone high
°F
75
72
85
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
VAV-3 — Excessive reheat during warm weather
Equation: Air flowing AND OAT > 78°F AND reheat valve > 52%.
Field
Value
Family
vav
Equipment kinds
vav
Operational gate
fan_running (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_t
outside-air-temp
required
reheat_valve_pct
reheat-valve
required
Plot series
oa_t → outside-air-temp
reheat_valve_pct → reheat-valve
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
reheat_oat
Warm OAT
°F
78
65
90
1
reheat_pct
Reheat frac
frac
0.52
0.1
1
0.02
flow_on_min
Airflow-on min
cfm
25
0
200
5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
VAV-4 — Damper stuck at full open
Equation: Air flowing AND damper > 97.5% sustained across the window.
Field
Value
Family
vav
Equipment kinds
vav
Operational gate
control_loop (startup 300s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
damper_pct
damper
required
Plot series
damper_pct → damper
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
full_open_pct
Full open frac
frac
0.975
0.8
1
0.005
sustain_hours
Sustain window
h
1.5
0.5
6
0.5
flow_on_min
Airflow-on min
cfm
25
0
200
5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
VAV-REHEAT — Reheat valve stuck / no temp rise
Equation: Air flowing AND reheat valve > 30% AND box discharge temp rises < 3°F above duct inlet (air from AHU) — stuck or failed reheat valve/coil.
Field
Value
Family
vav
Equipment kinds
vav
Operational gate
fan_running (startup 600s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
reheat_valve_pct
reheat-valve
required
vav_disch_t
vav-discharge-air-temp
required
vav_inlet_t
vav-inlet-air-temp
required
Plot series
reheat_valve_pct → reheat-valve
vav_disch_t → vav-discharge-air-temp
vav_inlet_t → vav-inlet-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
reheat_cmd
Reheat open frac
frac
0.3
0.1
1
0.05
min_rise
Min temp rise
°F
3
0.5
15
0.5
flow_on_min
Airflow-on min
cfm
25
0
200
5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
VAV-7 — Min airflow / fixed high flow
Equation: Flow below min SP (when mapped), OR airflow stays flat (low rolling std) at a high mean while air is on (mins too high / box never modulates), OR min_flow_sp itself is excessively high.
Field
Value
Family
vav
Equipment kinds
vav
Operational gate
fan_running (startup 300s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
zone_flow
zone-airflow
required
Plot series
zone_flow → zone-airflow
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
flow_on_min
Airflow-on min
cfm
25
0
200
5
fixed_flow_max_std
Fixed-flow max std
cfm
15
1
80
1
fixed_flow_min_mean
Fixed-flow min mean
cfm
200
50
2000
10
high_min_flow_sp
High min-flow SP
cfm
250
50
2000
10
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
5 · Central plant
CHW-1 — Low chilled-water ΔT
Equation: Pump on AND (CHWR − CHWS) < 4°F.
Field
Value
Family
plant
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 900s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
chw_supply_t
chilled-water-supply-temp
required
chw_return_t
chilled-water-return-temp
required
Plot series
chw_supply_t → chilled-water-supply-temp
chw_return_t → chilled-water-return-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
min_dt
Min ΔT
°F
4
1
12
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
RCx chw_reset_scatter — CHW leave vs web OAT; motor weekly uses pump/status not leave-temp.
CHW-2 — DP below SP at max pump speed
Equation: Pump ≥ 87% AND CHW DP < DP SP − 2.2.
Field
Value
Family
plant
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
chw_dp
chw-diff-pressure
required
chw_dp_sp
chw-diff-pressure-sp
required
chw_pump_cmd
chw-pump-cmd
required
Plot series
chw_dp → chw-diff-pressure
chw_dp_sp → chw-diff-pressure-sp
chw_pump_cmd → chw-pump-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
dp_margin
DP margin
psi
2.2
0.5
6
0.1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Plant motor weekly / chiller runtime — status/pump proof.
CHW-3 — Plant supply temp outside deadband
Equation: Pump on AND |CHWS − CHWS SP| > 2.2°F.
Field
Value
Family
plant
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 600s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
chw_supply_t
chilled-water-supply-temp
required
chw_supply_t_sp
chilled-water-supply-temp-sp
required
chw_pump_cmd
chw-pump-cmd
required
Plot series
chw_supply_t → chilled-water-supply-temp
chw_supply_t_sp → chilled-water-supply-temp-sp
chw_pump_cmd → chw-pump-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
sp_band
SP band
°F
2.2
0.5
6
0.1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
CHW-4 — Flow high at max pump
Equation: Pump ≥ 87% AND CHW flow > 1100 gpm.
Field
Value
Family
plant
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 300s)
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
chw_flow
chw-flow
required
chw_pump_cmd
chw-pump-cmd
required
Plot series
chw_flow → chw-flow
chw_pump_cmd → chw-pump-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
flow_hi
Flow high
gpm
1100
200
3000
50
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Fault hours / % on Results + FDD DOCX card; RCx overlays only if roles match a preset.
CW-OPT-1 — Condenser water not optimized vs wet-bulb
Equation: CW supply significantly colder than web wet-bulb + design approach (Stull WB) — tower over-cooling / not optimized.
Field
Value
Family
plant
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 600s)
Default confirm
900s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
cw_supply_t
condenser-water-supply-temp
required
Plot series
cw_supply_t → condenser-water-supply-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
cw_approach
Design approach
°F
7
3
15
0.5
cw_slack
Slack below target
°F
2
0.5
6
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
RCx cw_reset_scatter uses cw_supply_t vs web wet-bulb.
6 · Heat pump
HP-1 — Discharge cold when heating
Equation: Fan on, zone < 69°F, discharge SAT < 85°F.
Field
Value
Family
heatpump
Equipment kinds
heatpump
Operational gate
compressor (startup 600s)
Default confirm
600s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
sat
discharge-air-temp
required
zone_t
zone-air-temp
required
fan_cmd
fan-cmd
required
Plot series
sat → discharge-air-temp
zone_t → zone-air-temp
fan_cmd → fan-cmd
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
min_sat
Min heating SAT
°F
85
70
110
1
zone_cold
Zone cold
°F
69
60
72
0.5
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Mech-cooling OAT bins can use DX/compressor roles.
7 · Weather / OAT
WX-1 — OA temperature spike
Equation: OAT sample-to-sample jump > 16°F.
Field
Value
Family
weather
Equipment kinds
weather
Operational gate
always
Default confirm
300s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
oa_t
outside-air-temp
required
Plot series
oa_t → outside-air-temp
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
spike_limit
Spike limit
°F
16
4
40
1
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Weather family; web OAT enrich on weather frame.
8 · Trim & respond
TRIM-1 — Duct static trim advisory
Equation: Duct static high (> 1.35 in.w.c.) while VAV pressure requests are low.
Field
Value
Family
trim
Equipment kinds
ahu
Operational gate
fan_running (startup 300s)
Default confirm
1800s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
duct_static
duct-static-pressure
required
vav_press_req_sum
vav-pressure-request-sum
required
Plot series
duct_static → duct-static-pressure
vav_press_req_sum → vav-pressure-request-sum
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
Duct static / pressure trim requests; related to duct-static box RCx.
TRIM-3 — HWST trim advisory
Equation: HW supply > 160°F while reset requests are low.
Field
Value
Family
trim
Equipment kinds
boiler
Operational gate
hydronic_flow (startup 600s)
Default confirm
1800s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
hw_supply_t
hot-water-supply-temp
required
hw_reset_req_sum
hw-reset-request-sum
required
Plot series
hw_supply_t → hot-water-supply-temp
hw_reset_req_sum → hw-reset-request-sum
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
HW reset requests; RCx hw_reset_scatter.
TRIM-4 — CHW plant reset advisory
Equation: CHW supply < 45°F while reset requests are low.
Field
Value
Family
trim
Equipment kinds
chiller
Operational gate
hydronic_flow (startup 600s)
Default confirm
1800s
Sweep
—
Points → Haystack tags (this chart)
Cookbook role
Haystack-like tag
Requirement
chw_supply_t
chilled-water-supply-temp
required
chw_reset_req_sum
chw-reset-request-sum
required
Plot series
chw_supply_t → chilled-water-supply-temp
chw_reset_req_sum → chw-reset-request-sum
confirmed_fault swim lane (bool shade) when the rule was run
Sliders (tune params)
Key
Label
Unit
Default
Min
Max
Step
confirm_min
Fault confirm delay
min
5
0
60
1
Analytics / related views
CHW reset requests; RCx chw_reset_scatter.
Appendix A — COOKBOOK_TO_HAYSTACK_POINT (canonical export)
Cookbook role
Haystack-like tag
chw_dp
chw-diff-pressure
chw_dp_sp
chw-diff-pressure-sp
chw_flow
chw-flow
chw_pump_cmd
chw-pump-cmd
chw_reset_req_sum
chw-reset-request-sum
chw_return_t
chilled-water-return-temp
chw_supply_t
chilled-water-supply-temp
chw_supply_t_sp
chilled-water-supply-temp-sp
clg_coil_enter_t
cooling-coil-entering-temp
clg_coil_leave_t
cooling-coil-leaving-temp
clg_valve_pct
cooling-valve
cw_supply_t
condenser-water-supply-temp
damper_pct
damper
duct_static
duct-static-pressure
duct_static_sp
duct-static-pressure-sp
fan_cmd
fan-cmd
fan_status
fan-status
htg_coil_enter_t
heating-coil-entering-temp
htg_coil_leave_t
heating-coil-leaving-temp
htg_valve_pct
heating-valve
hw_reset_req_sum
hw-reset-request-sum
hw_return_t
hot-water-return-temp
hw_supply_t
hot-water-supply-temp
loop_enabled
loop-enabled
mat
mixed-air-temp
min_flow_sp
min-flow-sp
oa_damper_pct
outside-air-damper
oa_t
outside-air-temp
occ_mode
occupied
preheat_leave_t
preheat-leaving-temp
rat
return-air-temp
reheat_valve_pct
reheat-valve
sat
discharge-air-temp
sat_sp
discharge-air-temp-sp
vav_disch_t
vav-discharge-air-temp
vav_inlet_t
vav-inlet-air-temp
vav_press_req_sum
vav-pressure-request-sum
vav_total_flow
vav-total-airflow
wx_oa_t
web-outside-air-temp
zone_flow
zone-airflow
zone_t
zone-air-temp
Appendix B — Extended Haystack-style names used in this catalog
These roles appear on rules but are not yet keys in COOKBOOK_TO_HAYSTACK_POINT.
Prefer adding them to the dict when you next touch mapping exports.
Cookbook role
Suggested Haystack-like tag
airflow_proof
airflow-proof
compressor_status
compressor-status
cool_stage
cool-stage
dx_cool_cmd
dx-cool-cmd
dx_cooling
dx-cooling
dx_stage
dx-stage
fan_current
fan-current
fan_power
fan-power
fan_speed_feedback
fan-speed-feedback
pump_status
pump-status
Appendix C — Related RCx presets (not the 50)
See RCX_PLOTS.md. Reset scatters / duct-static box share roles with plant/AHU rules above.
Appendix D — Building-level analytics (not per-rule charts)
View
Where
Roles / inputs
Motor weekly runtime
Overview / Analytics
fan/pump/compressor status preferred
Mech-cooling OAT bins
Overview / Analytics
plant pump/status or DX compressor; web OAT; never CHW valve %