Fix a UPS repeatedly tripping a bonded-neutral generator's GFI/GFCI outlets
  1. Be sure there is no fault in the UPS, or conduction from neutral or hot to local ground of any metal.
  2. Remove the ground pin's connection to the generator from the UPS only with a cheater.
  3. Do not ground the UPS or anything connected to it referenced to the generator's ground.

Alternatively, de-bond a bonded-neutral generator and ground the generator's ground to Earth ground. Once debonded, a generator has to be treated differently and always grounded.