# This file is part of eDisGo, a python package for distribution grid | |
# analysis and optimization. | |
# | |
# It is developed in the project open_eGo: https://openegoproject.wordpress.com | |
# | |
# eDisGo lives on github: https://github.com/openego/edisgo/ | |
# The documentation is available on RTD: http://edisgo.readthedocs.io | |
[grid_expansion_standard_equipment] | |
# standard equipment | |
# ================== | |
# Standard equipment for grid expansion measures. Source: Rehtanz et. al.: "Verteilnetzstudie für das Land Baden-Württemberg", 2017. | |
hv_mv_transformer = 40 MVA | |
mv_lv_transformer = 630 kVA | |
mv_line = NA2XS2Y 3x1x185 RM/25 | |
lv_line = NAYY 4x1x150 | |
[grid_expansion_allowed_voltage_deviations] | |
# allowed voltage deviations | |
# ========================== | |
# COMBINED MV+LV | |
# -------------- | |
# hv_mv_trafo_offset: | |
# offset which is set at HV-MV station | |
# (pos. if op. voltage is increased, neg. if decreased) | |
hv_mv_trafo_offset = 0.04 | |
# hv_mv_trafo_control_deviation: | |
# control deviation of HV-MV station | |
# (always pos. in config; pos. or neg. usage depending on case in edisgo) | |
hv_mv_trafo_control_deviation = 0.0 | |
# mv_lv_max_v_deviation: | |
# max. allowed voltage deviation according to DIN EN 50160 | |
# caution: offset and control deviation at HV-MV station must be considered in calculations! | |
mv_lv_feedin_case_max_v_deviation = 0.1 | |
mv_lv_load_case_max_v_deviation = 0.1 | |
# MV ONLY | |
# ------- | |
# mv_load_case_max_v_deviation: | |
# max. allowed voltage deviation in MV grids (load case) | |
mv_load_case_max_v_deviation = 0.065 | |
# mv_feedin_case_max_v_deviation: | |
# max. allowed voltage deviation in MV grids (feedin case) | |
# according to BDEW | |
mv_feedin_case_max_v_deviation = 0.02 | |
# LV ONLY | |
# ------- | |
# max. allowed voltage deviation in LV grids (load case) | |
lv_load_case_max_v_deviation = 0.065 | |
# max. allowed voltage deviation in LV grids (feedin case) | |
# according to VDE-AR-N 4105 | |
lv_feedin_case_max_v_deviation = 0.03 | |
# max. allowed voltage deviation in MV/LV stations (load case) | |
mv_lv_station_load_case_max_v_deviation = 0.01 | |
# max. allowed voltage deviation in MV/LV stations (feedin case) | |
mv_lv_station_feedin_case_max_v_deviation = 0.01 | |
[grid_expansion_load_factors] | |
# load factors | |
# ============ | |
# Source: Rehtanz et. al.: "Verteilnetzstudie für das Land Baden-Württemberg", 2017. | |
mv_load_case_transformer = 0.5 | |
mv_load_case_line = 0.5 | |
mv_feedin_case_transformer = 1.0 | |
mv_feedin_case_line = 1.0 | |
lv_load_case_transformer = 1.0 | |
lv_load_case_line = 1.0 | |
lv_feedin_case_transformer = 1.0 | |
lv_feedin_case_line = 1.0 | |
# costs | |
# ============ | |
[costs_cables] | |
# costs in kEUR/km | |
# costs for cables without earthwork are taken from [1] (costs for standard | |
# cables are used here as representative since they have average costs), costs | |
# including earthwork are taken from [2] | |
# [1] https://www.bundesnetzagentur.de/SharedDocs/Downloads/DE/Sachgebiete/Energie/Unternehmen_Institutionen/Netzentgelte/Anreizregulierung/GA_AnalytischeKostenmodelle.pdf?__blob=publicationFile&v=1 | |
# [2] https://shop.dena.de/fileadmin/denashop/media/Downloads_Dateien/esd/9100_dena-Verteilnetzstudie_Abschlussbericht.pdf | |
# costs including earthwork costs depend on population density according to [2] | |
# here "rural" corresponds to a population density of <= 500 people/km² | |
# and "urban" corresponds to a population density of > 500 people/km² | |
lv_cable = 9 | |
lv_cable_incl_earthwork_rural = 60 | |
lv_cable_incl_earthwork_urban = 100 | |
mv_cable = 20 | |
mv_cable_incl_earthwork_rural = 80 | |
mv_cable_incl_earthwork_urban = 140 | |
[costs_transformers] | |
# costs in kEUR, source: DENA Verteilnetzstudie | |
lv = 10 | |
mv = 1000 |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
2011-05-01 00:00:00 | 0.0 | |
---|---|---|
2011-05-01 01:00:00 | 0.0 | |
2011-05-01 02:00:00 | 0.0 | |
2011-05-01 03:00:00 | 0.0 | |
2011-05-01 04:00:00 | 0.0 | |
2011-05-01 05:00:00 | 0.0 | |
2011-05-01 06:00:00 | 0.0 | |
2011-05-01 07:00:00 | 0.0 | |
2011-05-01 08:00:00 | 0.0 | |
2011-05-01 09:00:00 | 2300.0 | |
2011-05-01 10:00:00 | 2300.0 | |
2011-05-01 11:00:00 | 3000.0 | |
2011-05-01 12:00:00 | 3600.0 | |
2011-05-01 13:00:00 | 4000.0 | |
2011-05-01 14:00:00 | 3300.0 | |
2011-05-01 15:00:00 | 3300.0 | |
2011-05-01 16:00:00 | 1000.0 | |
2011-05-01 17:00:00 | 0.0 | |
2011-05-01 18:00:00 | 0.0 | |
2011-05-01 19:00:00 | 0.0 | |
2011-05-01 20:00:00 | 0.0 | |
2011-05-01 21:00:00 | 0.0 | |
2011-05-01 22:00:00 | 0.0 | |
2011-05-01 23:00:00 | 0.0 |