Instantly share code, notes, and snippets.

Embed
What would you like to do?
registers:
- name: L1 Voltage
unit_of_measurement: V
register: 0
data_type: float
precision: 2
count: 2
- name: L2 Voltage
unit_of_measurement: V
register: 2
data_type: float
precision: 2
count: 2
- name: L3 Voltage
unit_of_measurement: V
register: 4
data_type: float
precision: 2
count: 2
- name: L1 Current
unit_of_measurement: A
register: 6
data_type: float
precision: 2
count: 2
- name: L2 Current
unit_of_measurement: A
register: 8
data_type: float
precision: 2
count: 2
- name: L3 Current
unit_of_measurement: A
register: 10
data_type: float
precision: 2
count: 2
- name: L1 Power
unit_of_measurement: W
register: 12
data_type: float
precision: 2
count: 2
- name: L2 Power
unit_of_measurement: W
register: 14
data_type: float
precision: 2
count: 2
- name: L3 Power
unit_of_measurement: W
register: 16
data_type: float
precision: 2
count: 2
- name: L1 VA
unit_of_measurement: VA
register: 18
data_type: float
precision: 2
count: 2
- name: L2 VA
unit_of_measurement: VA
register: 20
data_type: float
precision: 2
count: 2
- name: L3 VA
unit_of_measurement: VA
register: 22
data_type: float
precision: 2
count: 2
- name: L1 VAr
unit_of_measurement: VAr
register: 24
data_type: float
precision: 2
count: 2
- name: L2 VAr
unit_of_measurement: VAr
register: 26
data_type: float
precision: 2
count: 2
- name: L3 VAr
unit_of_measurement: VAr
register: 28
data_type: float
precision: 2
count: 2
- name: L1 PowerFactor
unit_of_measurement: '%'
register: 30
data_type: float
precision: 2
count: 2
- name: L2 PowerFactor
unit_of_measurement: '%'
register: 32
data_type: float
precision: 2
count: 2
- name: L3 PowerFactor
unit_of_measurement: '%'
register: 34
data_type: float
precision: 2
count: 2
- name: L1 Phase Angle
unit_of_measurement: °
register: 36
data_type: float
precision: 2
count: 2
- name: L2 Phase Angle
unit_of_measurement: °
register: 38
data_type: float
precision: 2
count: 2
- name: L3 Phase Angle
unit_of_measurement: °
register: 40
data_type: float
precision: 2
count: 2
- name: Average Volts
unit_of_measurement: V
register: 42
data_type: float
precision: 2
count: 2
- name: Average Current
unit_of_measurement: A
register: 46
data_type: float
precision: 2
count: 2
- name: Sum of Current
unit_of_measurement: A
register: 48
data_type: float
precision: 2
count: 2
- name: Total System Power
unit_of_measurement: W
register: 52
data_type: float
precision: 2
count: 2
- name: Total System VA
unit_of_measurement: VA
register: 56
data_type: float
precision: 2
count: 2
- name: Total System VAr
unit_of_measurement: VAr
register: 60
data_type: float
precision: 2
count: 2
- name: Total System Power Factor
register: 62
data_type: float
precision: 2
count: 2
- name: Total System Phase Angle
unit_of_measurement: °
register: 66
data_type: float
precision: 2
count: 2
- name: Supply Frequency
unit_of_measurement: Hz
register: 70
data_type: float
precision: 2
count: 2
- name: Import Watt Hours
unit_of_measurement: kWh
register: 72
data_type: float
precision: 2
count: 2
- name: Export Watt Hours
unit_of_measurement: kWh
register: 74
data_type: float
precision: 2
count: 2
- name: Import VArh
unit_of_measurement: kVArh
register: 76
data_type: float
precision: 2
count: 2
- name: Export VArh
unit_of_measurement: kVArh
register: 78
data_type: float
precision: 2
count: 2
- name: VAh since last reset
unit_of_measurement: kVAh
register: 80
data_type: float
precision: 2
count: 2
- name: Ah since last reset
unit_of_measurement: Ah
register: 82
data_type: float
precision: 2
count: 2
- name: Total System Power Demand
unit_of_measurement: W
register: 84
data_type: float
precision: 2
count: 2
- name: Maximum total system power demand
unit_of_measurement: VA
register: 86
data_type: float
precision: 2
count: 2
- name: Total system VA demand
unit_of_measurement: VA
register: 100
data_type: float
precision: 2
count: 2
- name: Maximum total system VA demand
unit_of_measurement: VA
register: 102
data_type: float
precision: 2
count: 2
- name: Neutral Current Demand
unit_of_measurement: A
register: 104
data_type: float
precision: 2
count: 2
- name: Maximum Neutral Current Demand
unit_of_measurement: A
register: 106
data_type: float
precision: 2
count: 2
- name: L1-L2 Voltage
unit_of_measurement: V
register: 200
data_type: float
precision: 2
count: 2
- name: L2-L3 Voltage
unit_of_measurement: V
register: 202
data_type: float
precision: 2
count: 2
- name: L3-L1 Voltage
unit_of_measurement: V
register: 204
data_type: float
precision: 2
count: 2
- name: Average L-L Voltage
unit_of_measurement: V
register: 206
data_type: float
precision: 2
count: 2
- name: Neutral Current
unit_of_measurement: A
register: 224
data_type: float
precision: 2
count: 2
- name: L1-N Volts THD
unit_of_measurement: '%'
register: 234
data_type: float
precision: 2
count: 2
- name: L2-N Volts THD
unit_of_measurement: '%'
register: 236
data_type: float
precision: 2
count: 2
- name: L3-N Volts THD
unit_of_measurement: '%'
register: 238
data_type: float
precision: 2
count: 2
- name: L1 Current THD
unit_of_measurement: '%'
register: 240
data_type: float
precision: 2
count: 2
- name: L2 Current THD
unit_of_measurement: '%'
register: 242
data_type: float
precision: 2
count: 2
- name: L3 Current THD
unit_of_measurement: '%'
register: 244
data_type: float
precision: 2
count: 2
- name: Average L-N Volts THD
unit_of_measurement: '%'
register: 248
data_type: float
precision: 2
count: 2
- name: Average Line Current THD
unit_of_measurement: '%'
register: 250
data_type: float
precision: 2
count: 2
- name: Total System Power Factor
unit_of_measurement: °
register: 254
data_type: float
precision: 2
count: 2
- name: L1 Current Demand
unit_of_measurement: A
register: 258
data_type: float
precision: 2
count: 2
- name: L2 Current Demand
unit_of_measurement: A
register: 260
data_type: float
precision: 2
count: 2
- name: L3 Current Demand
unit_of_measurement: A
register: 262
data_type: float
precision: 2
count: 2
- name: L1 Max Current demand
unit_of_measurement: A
register: 264
data_type: float
precision: 2
count: 2
- name: L2 Max Current demand
unit_of_measurement: A
register: 266
data_type: float
precision: 2
count: 2
- name: L3 Max Current demand
unit_of_measurement: A
register: 268
data_type: float
precision: 2
count: 2
- name: L1-L2 Volts THD
unit_of_measurement: '%'
register: 334
data_type: float
precision: 2
count: 2
- name: L2-L3 Volts THD
unit_of_measurement: '%'
register: 336
data_type: float
precision: 2
count: 2
- name: L3-L1 Volts THD
unit_of_measurement: '%'
register: 338
data_type: float
precision: 2
count: 2
- name: Average L-N THD
unit_of_measurement: '%'
register: 340
data_type: float
precision: 2
count: 2
- name: Total kWh
unit_of_measurement: kWh
register: 342
data_type: float
precision: 2
count: 2
- name: Total kVArh
unit_of_measurement: kVArh
register: 344
data_type: float
precision: 2
count: 2
- name: L1 Import kWh
unit_of_measurement: kWh
register: 346
data_type: float
precision: 2
count: 2
- name: L2 Import kWh
unit_of_measurement: kWh
register: 348
data_type: float
precision: 2
count: 2
- name: L3 Import kWh
unit_of_measurement: kWh
register: 350
data_type: float
precision: 2
count: 2
- name: L1 Export kWh
unit_of_measurement: kWh
register: 352
data_type: float
precision: 2
count: 2
- name: L2 Export kWh
unit_of_measurement: kWh
register: 354
data_type: float
precision: 2
count: 2
- name: L3 Export kWh
unit_of_measurement: kWh
register: 356
data_type: float
precision: 2
count: 2
- name: L1 Total kWh
unit_of_measurement: kWh
register: 358
data_type: float
precision: 2
count: 2
- name: L2 Total kWh
unit_of_measurement: kWh
register: 360
data_type: float
precision: 2
count: 2
- name: L3 Total kWh
unit_of_measurement: kWh
register: 362
data_type: float
precision: 2
count: 2
- name: L1 Import kVArh
unit_of_measurement: kVArh
register: 364
data_type: float
precision: 2
count: 2
- name: L2 Import kVArh
unit_of_measurement: kVArh
register: 366
data_type: float
precision: 2
count: 2
- name: L3 Import kVArh
unit_of_measurement: kVArh
register: 368
data_type: float
precision: 2
count: 2
- name: L1 Export kVArh
unit_of_measurement: kVArh
register: 370
data_type: float
precision: 2
count: 2
- name: L2 Export kVArh
unit_of_measurement: kVArh
register: 372
data_type: float
precision: 2
count: 2
- name: L3 Export kVArh
unit_of_measurement: kVArh
register: 374
data_type: float
precision: 2
count: 2
- name: L1 Total kVArh
unit_of_measurement: kVArh
register: 376
data_type: float
precision: 2
count: 2
- name: L2 Total kVArh
unit_of_measurement: kVArh
register: 378
data_type: float
precision: 2
count: 2
- name: L3 Total kVArh
unit_of_measurement: kVArh
register: 380
data_type: float
precision: 2
count: 2
@robermf

This comment has been minimized.

robermf commented Jul 24, 2018

Hello Sean,
I came here from your site. First of all say thank you.

I just got an Efergy energy monitor system and it's really inaccurate (it shows reactive energy + active energy). After looking for several hours I found your solution like the best option.

I would like to use a RS485 Modbus to wireless made by Eastron, so I think it will work fine.

I am a new on Home Assistant and even newer with the Modbus... My question is: Once I made the TCP connection, how can I connect to the TCP Gateway/SDM630?

I see some people connect the SDM630 to a Raspberry Pi via USB. It would be possible to get data from that Rasperry Pi into Home Assistant?

Thank you again.

@mitchese

This comment has been minimized.

Owner

mitchese commented Oct 25, 2018

The Wireless Eastron things seem to be (at least the ones I found), all LoRa. This should abstract all the RS485 stuff away, but I'm not sure, never used these yet.

The RS485 <--> TCP Gateway is physically wired to the power meter via two wires (RS485), and has ethernet coming out of it. From this point, everything is then TCP, so home assistant has nothing physically connected to the power meter; it just makes the calls over the network to the gateway.

I think what you're referring to with a Raspberry Pi via USB is replacing the RS485<-->TCP gateway with an RS485<-->UART, then hooking this to the Raspberry via USB. In this case, then raspberry pi would either have to have home assistant directly on it, or run some sort of software to provide the UART(/RS485/power meter) connection to the internet. This is then going in the direction of a DIY Gateway.

If you have specific products you're looking at, please post the links to help me understand what you're looking at.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment