Liquid cooling 1MW DC Calculations
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Servers | |
2.52A * 12V = 30.24W | |
30.24W * 8 = 241.92W | |
30 servers * 241.92W = 7257.6W | |
30 servers * 241.92W * 0.8 = 5806.08W | |
30 servers * 241.92W * 0.2 = 1451.52W | |
7257.6W - 750W = 6507.6W | |
1451.52W - 750W = 701.52W | |
12V * 0.12A = 1.44W | |
1.44W * 8 = 11.52W | |
Power Reduction benefit | |
(241.92W / 1200W) * 100 = 20.16% | |
1MW * 1000kW/MW * 0.2016 = 201.6kW | |
1MW * 1000kW/MW * 0.7094 = 798.4kW [IT Compute] | |
201.6kW + 300kW = 501.6kW [Air movement] | |
1MW * 1000kW/MW / 1.200kW/Server = 833.33 Servers | |
1200W - 241.92W = 958.08W | |
1200W - 241.92W + 11.52W = 969.6W [Liquid cooled server power] | |
652W / 15 = 43.46W | |
11.52W + 43.46W = 54.98W | |
969.6W + 43.6W = 1013.06W [Liquid cooled server power + CDU burden] | |
(11.52W + 43.46W) / 969.6W * 100 = 5.670% [Fan overhead for liquid cooled server + HRU] | |
1000kW / 1.01306kW/Server = 987 servers | |
200kW / 1000kW * 100 = 20% [Facility power reduction] | |
1MW * 1000kW/MW - (833 servers * 1013.6W/1000) = 155.67kW [Critical IT power reduction] | |
200kW + 155.67kW = 355.67kW [Total energy savings converting to liquid cooling] | |
155.67kW / 1.01306kW/Server = 153 additional servers | |
153 / 833 * 100 = 18.36% server capacity increase |