Program Version,EnergyPlus, Version 9.2.0-8ec2c2deb6, YMD=2019.08.28 09:20,
** Warning ** Timestep: Requested number (1) is less than the suggested minimum of 4.
** ~~~ ** Please see entry for Timestep in Input/Output Reference for discussion of considerations.
** Warning ** GetHTSurfaceData: Surfaces with interface to Ground found but no "Ground Temperatures" were input.
** ~~~ ** Found first in surface=FOUNDATIONWALL
** ~~~ ** Defaults, constant throughout the year of (18.0) will be used.
** Warning ** SurfaceProperty:ExposedFoundationPerimeter: SLAB, TOTALEXPOSEDPERIMETER set as calculation method, but a value has been set for Exposed Perimeter Fraction. This value will be ignored.
************* Note that the following warning(s) may/will occur if you have not enclosed your zone completely.
** Warning ** Entered Zone Volumes differ from calculated zone volume(s).
** ~~~ ** ...use Output:Diagnostics,DisplayExtraWarnings; to show more details on individual zones.
** Warning ** CalculateZoneVolume: 3 zones are not fully enclosed. For more details use: Output:Diagnostics,DisplayExtrawarnings;
** Warning ** Surfaces in Zone/Enclosure="UNVENTED ATTIC" do not define an enclosure.
** ~~~ ** Number of surfaces <= 3, view factors are set to force reciprocity but may not fulfill completeness.
** ~~~ ** Reciprocity means that radiant exchange between two surfaces will match and not lead to an energy loss.
** ~~~ ** Completeness means that all of the view factors between a surface and the other surfaces in a zone add up to unity.
** ~~~ ** So, when there are three or less surfaces in a zone, EnergyPlus will make sure there are no losses of energy but
** ~~~ ** it will not exchange the full amount of radiation with the rest of the zone as it would if there was a completed enclosure.
** Warning ** Surfaces in Zone/Enclosure="UNVENTED ATTIC" do not define an enclosure.
** ~~~ ** Number of surfaces <= 3, view factors are set to force reciprocity but may not fulfill completeness.
** ~~~ ** Reciprocity means that radiant exchange between two surfaces will match and not lead to an energy loss.
** ~~~ ** Completeness means that all of the view factors between a surface and the other surfaces in a zone add up to unity.
** ~~~ ** So, when there are three or less surfaces in a zone, EnergyPlus will make sure there are no losses of energy but
** ~~~ ** it will not exchange the full amount of radiation with the rest of the zone as it would if there was a completed enclosure.
** Warning ** The Standard Ratings is calculated for Coil:Cooling:DX:SingleSpeed = CENTRAL AC CLG COIL but not at the AHRI test condition due to curve out of bound.
** ~~~ ** Review the Standard Ratings calculations in the Engineering Reference for this coil type. Also, use Output:Diagnostics, DisplayExtraWarnings for further guidance.
** Warning ** Water heater = WATER HEATER: Recovery Efficiency and Energy Factor could not be calculated during the test for standard ratings
** ~~~ ** Setpoint was never recovered and/or heater never turned on
** Warning ** Check input. Pump nominal power or motor efficiency is set to 0, for pump=PUMP VARIABLE SPEED 1
************* Testing Individual Branch Integrity
************* All Branches passed integrity testing
************* Testing Individual Supply Air Path Integrity
************* All Supply Air Paths passed integrity testing
************* Testing Individual Return Air Path Integrity
************* All Return Air Paths passed integrity testing
************* No node connection errors were found.
************* Beginning Simulation
** Warning ** GetSpecificHeatGlycol: Temperature is out of range (too low) for fluid [WATER] specific heat supplied values **
** ~~~ ** ..Called From:UpdatePlantLoopInterface,Temperature=[-2.16], supplied data range=[0.00,125.00]
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=01/01 00:00 - 01:00
** Warning ** GetDensityGlycol: Temperature is out of range (too low) for fluid [WATER] density **
** ~~~ ** ..Called From:NodeReportingCalc:NODE 17,Temperature=[-2.16], supplied data range=[0.00,100.00]
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=01/01 00:00 - 01:00
** Warning ** CalcWaterThermalTankMixed: WaterHeater:Mixed = 'WATER HEATER': Temperature of tank < 2C indicates of possibility of freeze. Tank Temperature = 1.28 C.
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=01/02 04:00 - 05:00
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 04/03 13:00 - 14:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** ~~~ ** ...use Output:Diagnostics,DisplayExtraWarnings; to show more details on each max iteration exceeded.
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 04/20 15:00 - 16:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 04/30 09:00 - 10:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 05/09 14:00 - 15:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 05/10 08:00 - 09:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 05/13 09:00 - 10:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 05/15 04:00 - 05:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** CalcDoe2DXCoil: Coil:Cooling:DX:SingleSpeed="CENTRAL AC CLG COIL" - Air volume flow rate per watt of rated total cooling capacity is out of range at 6.763E-005 m3/s/W.
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=05/17 16:00 - 17:00
** ~~~ ** Expected range for VolumeFlowPerRatedTotalCapacity=[2.684E-005--6.713E-005]
** ~~~ ** Possible causes include inconsistent air flow rates in system components,
** ~~~ ** or variable air volume [VAV] system using incorrect coil type.
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 05/18 08:00 - 09:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 06/06 00:00 - 01:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 06/11 21:00 - 22:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 07/02 06:00 - 07:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 07/02 07:00 - 08:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 07/02 08:00 - 09:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at RUN PERIOD 1, 07/03 13:00 - 14:00
** ~~~ ** The solution for one or more of the Air Loop HVAC systems did not appear to converge
** Warning ** The resource referenced by LifeCycleCost:UsePriceEscalation= "U.S. AVG COMMERCIAL-ELECTRICITY" has no energy cost.
** ~~~ ** ... It is likely that the wrong resource is used. The resource should match the meter used in Utility:Tariff.
** Warning ** The resource referenced by LifeCycleCost:UsePriceEscalation= "U.S. AVG COMMERCIAL-DISTILLATE OIL" has no energy cost.
** ~~~ ** ... It is likely that the wrong resource is used. The resource should match the meter used in Utility:Tariff.
** Warning ** The resource referenced by LifeCycleCost:UsePriceEscalation= "U.S. AVG COMMERCIAL-RESIDUAL OIL" has no energy cost.
** ~~~ ** ... It is likely that the wrong resource is used. The resource should match the meter used in Utility:Tariff.
** Warning ** The resource referenced by LifeCycleCost:UsePriceEscalation= "U.S. AVG COMMERCIAL-NATURAL GAS" has no energy cost.
** ~~~ ** ... It is likely that the wrong resource is used. The resource should match the meter used in Utility:Tariff.
** Warning ** The resource referenced by LifeCycleCost:UsePriceEscalation= "U.S. AVG COMMERCIAL-COAL" has no energy cost.
** ~~~ ** ... It is likely that the wrong resource is used. The resource should match the meter used in Utility:Tariff.
************* Simulation Error Summary *************
************* There are 3 unused schedules in input.
************* There are 66 unused week schedules in input.
************* There are 39 unused day schedules in input.
************* Use Output:Diagnostics,DisplayUnusedSchedules; to see them.
*************
************* ===== Recurring Error Summary =====
************* The following recurring error messages occurred.
*************
************* ** Warning ** GetSpecificHeatGlycol: Temperature out of range (too low) for fluid [WATER] specific heat **
************* ** ~~~ ** This error occurred 99841 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
************* ** ~~~ ** Max=-5.144439E-004 {C} Min=-19.464834 {C}
*************
************* ** Warning ** GetDensityGlycol: Temperature out of range (too low) for fluid [WATER] density **
************* ** ~~~ ** This error occurred 58276 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
************* ** ~~~ ** Max=-5.144439E-004 {C} Min=-19.464834 {C}
*************
************* ** Warning ** WaterHeater:Mixed = 'WATER HEATER': Temperature of tank < 2C indicates of possibility of freeze
************* ** ~~~ ** This error occurred 19599 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
************* ** ~~~ ** Max=1.99991 {C} Min=-19.464834 {C}
*************
************* ** Warning ** Plant loop falling below lower temperature limit, PlantLoop="DHW LOOP"
************* ** ~~~ ** This error occurred 872 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
************* ** ~~~ ** Min=-19.021018
*************
************* ** Warning ** CalcDoe2DXCoil: Coil:Cooling:DX:SingleSpeed="CENTRAL AC CLG COIL" - Air volume flow rate per watt of rated total cooling capacity is out of range error continues...
************* ** ~~~ ** This error occurred 15190 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
************* ** ~~~ ** Max=6.958738E-005 Min=6.741609E-005
*************
************* ** Warning ** SimHVAC: Exceeding Maximum iterations for all HVAC loops, during RUN PERIOD 1 continues
************* ** ~~~ ** This error occurred 21 total times;
************* ** ~~~ ** during Warmup 0 times;
************* ** ~~~ ** during Sizing 0 times.
*************
************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.
************* EnergyPlus Completed Successfully-- 193829 Warning; 0 Severe Errors; Elapsed Time=00hr 00min 35.28sec