sjkjs commented Aug 13, 2023

I ran the drain wire out of one of the RJ45 plugs and just connected that to the same ground as the surge suppressor.

Thanks for the explanation. That all makes sense.

I'm using a Netgear GC110P PoE switch which doesn't have the shield grounded and also doesn't provide a grounding screw. The shield seems to be disconnected from everything.

I like your idea of using one of the spare RJ45 ports and running a drain wire to somewhere else that does have a ground. I might look at doing that too.

@darconeous
Copy link
Author

For what it's worth, I grounded my 200' setup at two places:

  1. Using a Cat-6 surge protector close to the antenna, ~120ft away from the house. This grounds the shielding and provides an arc path to ground for the twisted pairs.
  2. Grounding the shielding at the service entrance for the house, no surge.

The ground at the antenna is it's own ground spike. The ground at the house is the shared house ground (luckily I could run a wire to that on the exterior of the house). Unclear if I'm going to ultimately have galvanic problems. Hopefully not. Resistance between the two independent ground spikes is fairly low.

Originally both ground points were going to be full CAT-6 surge protectors, but I was having trouble with them increasing the resistance slightly so at some point I decided to just ground the shielding at the service entrance. That was before I switched to 52V, so perhaps I should revisit that... I'm hesitant to cut the wire though, since I can't un-cut it if it doesn't work out.

@jbowler
Copy link

jbowler commented Oct 6, 2023

Resistance between the two independent ground spikes is fairly low.

I'm very interested in knowing what that resistance is :-)

@darconeous
Copy link
Author

I'm very interested in knowing what that resistance is :-)

If I remember correctly, it was a few ohms. I don't remember what it was exactly, I just remember thinking "wow, that's lower than I expected". I have an outlet nearby with a ground that is connected to the house ground (not the ground that the antenna is connected to) so one day I got curious and pulled out the multimeter. But a low resistance makes sense, we have a lot of minerals in our clay-type soil that also has considerable moisture content. And I really buried that rod quite well.

I'm curious now, we just had a lot of rain. I can check again tomorrow.

@crdiaz324
Copy link

Is it possible to use 2 of these making 2 custom Y cable to use only the 2 powered pairs of each injector?

Yes but you have to know exactly what you are doing and it's pointless since the Tycon, as documented above, works just fine so long as correct wire pairs are swapped. If you don't want to do that the one I posted links to on Amazon doesn't require the wire swap. Seriously though, the cable has to be cut with any of these solutions (except the two most recently posted) so attach the RJ45 modular plus and it really is no more difficult to crimp those on with the correct wire swap than it is to crimp them on without a wire swap. (Both are error prone of course.)

A single APOE03G costs the same as a single Tycon PoE (USD15 from Amazon, USD10+postage direct from Tycon).

I've successfully used the techcharmer.com kit with my modified dishy without having to cut or swap any wires. The process involved connecting the provided cable from the kit to the plug in the back of the dishy, and subsequently to the POE's power output. Then I connected the POE to my router utilizing a standard ethernet cable I acquired from Amazon. This setup has proven to be incredibly reliable, running seamlessly for approximately 4 to 5 months. The kit was roughly $30. Hard to beat that IMO.

@JustOneGuyHere
Copy link

JustOneGuyHere commented Oct 20, 2023 via email

@jbowler
Copy link

jbowler commented Oct 20, 2023

@JustOneGuyHere; @crdiaz324 was commenting on his previous post from July:

https://gist.github.com/darconeous/8c7899c4d2f849b881d6c43be55066ee?permalink_comment_id=4645398#gistcomment-4645398

It's worth noting that TechCharmer now sell that Tycon lookalike PSU with what appears to be YAOSHENG adapter I posted a link to (two posts down from the above). Here: https://techcharmer.com/collections/our-products/products/starlink-dc-adapter-kit The Amazon link I posted no longer works but it's here:

https://www.amazon.com/YAOSHENG-Rectangular-Adapter-Connect-Injector/dp/B0BYJTHX4P

It's a nice move by TechCharmer; they've undercut the YAOSHENG very expensive PSU ($81) with an adequate and well proven power supply (assuming it is one of the Tycons), but they certainly seem to be selling the YAOSHENG adapter as part of it. Everyone benefits. The only downside to the TechCharmer solution is that there is no surge protection that I can see, but there is none on the official StarLink router (aka incredibly expensive PSU) so far as I know.